Inspection
Inspection Details
Equipment ID
10970
10970
Inspection Date
3/20/2025
3/20/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
49f88d0f-8f67-430d-97d9-d3c706b72d6d
49f88d0f-8f67-430d-97d9-d3c706b72d6d
Location
Kirkpatrick Building
620 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 279-1010
620 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 279-1010
Owner
Attn: St. John Holdings
St. John Holdings
117 S 7th St, St. Joseph, MO 64501
Phone: (816) 279-1010
Alt Phone: (816) 261-8236
Email: stjohnholdings@yahoo.com
St. John Holdings
117 S 7th St, St. Joseph, MO 64501
Phone: (816) 279-1010
Alt Phone: (816) 261-8236
Email: stjohnholdings@yahoo.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Install permanent light fixture and switch in pit. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Pipes conveying liquids, vapors,gases not allowed in hoistway. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Install pit ladder with handrails extending 30 inches above landing | 7/15/2020 |
| conversion | conversion | n/a | No | No | Cover exposed motor leads in machine room. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Post current operating certificate. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Machine room door shall be self closing and self locking. | 7/15/2020 |
| conversion | conversion | n/a | No | No | No annual testing or inspection 2009 to 2001 and 2014 to 2017 per state website. No test tags on site for those years either. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Machine room fire extinguisher not certified. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Emergency light and bell do not operate. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Guard hoistway windows and mark HOISTWAY viewable from outside. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Provide maintenance control plan | 7/15/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | PROVIDE A SELF CLOSING / SELF LOCKING MACHINE ROOM DOOR | 7/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | INSTALL A PIT LIGHT AND A GFCI OUTLET | 5/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | INSTALL A PIT LADDER | 5/9/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | THE INSTALLED PHONE IS NOT WORKING | 3/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | DISPLAY STATE OPERATING CERTIFICATE IN MACHINE ROOM | 5/9/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE A WORKING IN CAR EMERGENCY PHONE | 5/12/2025 |