|
conversion
|
conversion
|
n/a
|
|
|
Need to install lighting at top of hoistway for machine room lighting
|
12/18/2019
|
|
conversion
|
conversion
|
n/a
|
|
|
Pit light not working
|
12/18/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
The pit light shall be operational.
|
10/2/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Operating certificate shall be posted in elevator. Note: Unit is an MRL and there is no machine room to post certificate in.
|
10/2/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Control spaces requires 19 foot candles of light in hoisway at controller.
|
10/2/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
3.26.10 (Auxiliary Power)(Re-Inspection)
|
x
|
|
Battery lowering shall work.
|
2/24/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency phone is not operational.
|
2/24/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an overspeed valve that is due for category 5 testing on or before the next annual inspection.
|
10/2/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Note: The displayed certificate is expired.
|
2/18/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
The pit light switch shall be fed from a separate branch circuit. Note: The pit lights are currently being fed from the switch leg of the hall lobby lights. This means the pit light switch will not turn on the pit lights unless the lobby lights are on. The pit light shall be fed from a separate branch circuit as required.
|
2/18/2026
|