Inspection
Inspection Details
Equipment ID
13083
13083
Inspection Date
3/26/2025
3/26/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Gregory Mason
Gregory Mason
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
5867b114-5ebd-4449-9b2f-a86f5609a2e7
5867b114-5ebd-4449-9b2f-a86f5609a2e7
Location
Friendly Temple Apartments Phase II
5521 WELLS AVE, SAINT LOUIS, MO
Phone: (314) 367-9700
5521 WELLS AVE, SAINT LOUIS, MO
Phone: (314) 367-9700
Owner
Attn: Executive Director, Joseph Hicks
Friendly Temple Apartments
5545 Wells Ave # 5521, St. Louis, MO 63112
Phone: (314) 867-8993
Email: joseph.hicks@standrews1.com
Friendly Temple Apartments
5545 Wells Ave # 5521, St. Louis, MO 63112
Phone: (314) 867-8993
Email: joseph.hicks@standrews1.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Empty drip pans, provide covers and remove oil from pit | 8/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair phone in car | 11/30/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Empty oil pans in pit and provide covers & remove oil from pit floor | 8/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Clean oil drip pans in pit and install covers | 8/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Clean oil drip pans in pit and install covers | 3/13/2025 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Oversoeed valve past due for full load testing | 3/13/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 3/13/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/14/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/26/2025 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Empty drain pans. | 3/26/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean the pit. | 3/26/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide existing battery backup lowering unit to work properly. | 3/26/2025 |