Inspection
Inspection Details
Equipment ID
19558
19558
Inspection Date
3/27/2025
3/27/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Paul Jaremko
Paul Jaremko
Relief Valve Pressure
485
485
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
10
10
External ID
6cd93d45-f150-4c98-8d04-8a3e08f61802
6cd93d45-f150-4c98-8d04-8a3e08f61802
Location
San Regis Apartments
1015 Faraon St, St. Joseph, MO
Phone: (816) 233-4513
1015 Faraon St, St. Joseph, MO
Phone: (816) 233-4513
Owner
Attn: Cathy Chavez
San Regis Apartments
1015 Faron St, St. Joseph, MO 64501
Phone: (816) 233-3002
Email: sanregis@molinemgt.com
San Regis Apartments
1015 Faron St, St. Joseph, MO 64501
Phone: (816) 233-3002
Email: sanregis@molinemgt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate. | 5/1/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency bell does not operate. | 12/20/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Water is leaking through the top of the hoistway enclosure and onto the top of the elevator. | 2/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Machine room door needs to be self locking and non-defeatable. | 2/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state operating certificate inside machine room | 2/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not provide two way communication | 2/15/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | Gas powered snowblower, container of gasoline, and bags of salt must be removed from elevator machine room. Non-elevator related material shall not be stored inside the machine room. Extreme fire hazard. | 2/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | x | No firefighter phase 2 operation panel behind locked cover on car operating panel. | 3/24/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 2.12.7 | No hoistway access operation provided. | 12/28/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 8.11.3.1.5(f) | Traveling cable needs to be replaced. Traveling cable is damaged due to moisture issue. | 12/28/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | Identify the inside of hoistway doors with a numeral | 12/28/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Post In Case of Fire Do Not Use Elevator signage next to hall button fixture at bottom landing. | 12/28/2022 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No maintenance control plan on site | 12/28/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | Identify inside of the hoistway door with a numeral | 4/17/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed | 4/17/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | x | 2.27.3.3.1(c) Door close button non functional must reinspect when issue is corrected. | 3/29/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | PROVIDE A WORKING IN CAR EMERGENCY PHONE | 3/17/2026 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.3.5 | x | BATTERY ENERGENCY LOWERING NOT WORKING | 3/17/2026 |