Inspection
Inspection Details
Equipment ID
2045
2045
Inspection Date
2/18/2025
2/18/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Clifford Miller
Clifford Miller
Relief Valve Pressure
340
340
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
24
24
External ID
211a1741-cf49-4088-bbe5-64f174b2ab25
211a1741-cf49-4088-bbe5-64f174b2ab25
Location
Lee's Summit High School
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
Owner
Attn: Nick Mathews
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2173
Email: nick.mathews@lsr7.net
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2173
Email: nick.mathews@lsr7.net
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | x | Emergency phone dropping call after connection. | 1/19/2021 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Fire service works, but won't reset with the key after testing. | 1/19/2021 |
MO Minimum : Elevators | (I) - Pits | (I)7 | Pit switch working, but incorrectly labeled. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Fire service testing log not up to date. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)2 Alterations | Fire sprinkler added in machine room during remodeling work. Remove, or provide a shunt trip device and heat detector in machine room. | |||
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | x | Sprinkler line for shunt trip not finished. | 1/18/2023 | |
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working. Line? | 4/1/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Shunt trip not overriding battery lowering. Needs relay added | 4/1/2024 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | x | Top of hoistway smoke sensor recalls elevator to wrong floor. Relay needed | 4/1/2024 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Machine room needs 110v receptical | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working. Bldg line. | 2/20/2024 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Machine room needs 110v gfci outlet | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working, alarm bell ok. | 8/27/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working, alarm bell ok. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Jack packing leaking, causing pit jug to overflow. |