Inspection
Inspection Details
Equipment ID
2047
2047
Inspection Date
2/18/2025
2/18/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Clifford Miller
Clifford Miller
Relief Valve Pressure
440
440
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
24
24
External ID
2793c534-2d65-41e4-9590-56469818f6d2
2793c534-2d65-41e4-9590-56469818f6d2
Location
Lee's Summit High School
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
Owner
Attn: Nick Mathews
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2173
Email: nick.mathews@lsr7.net
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2173
Email: nick.mathews@lsr7.net
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Overhead lighting in car inadequate, and unguarded. | |||
MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | x | Emergency phone not identifying location of call. | 1/19/2021 | |
MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | x | Emergency lights not working. | 1/19/2021 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Emergency phone not identifying the location. | 1/19/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working, alarm bell ok. | 1/19/2023 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | Connection loose on controller starter box din rail. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Fire service testing log not up to date. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Provide covers for FFS modules in machine room. | |||
A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Machine room door must be self-closing | |||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone not being answered | 4/1/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Shunt trip not overriding battery lowering. Need relay added | 4/1/2024 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | x | Top hoistway smoke sensor recalls elevator to wrong floor. Need relay added | 4/1/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working, alarm bell ok. |