Inspection
Inspection Details
Equipment ID
10248
10248
Inspection Date
3/24/2025
3/24/2025
Inspection Type
Alteration
Alteration
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Justin Scherer
Justin Scherer
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
68 / 275
68 / 275
Door Closing Force
Na
Na
External ID
da5ef00f-5c00-400f-8672-d18e1ffff06b
da5ef00f-5c00-400f-8672-d18e1ffff06b
Location
Metropolitan Square
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
Owner
Attn: Metropolitan Square LLC
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: sam.mauer@am.jll.com
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: sam.mauer@am.jll.com
Billing
Attn: Jones Lang LaSalle
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 436-1212
Email: melissa.walker@jll.com
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 436-1212
Email: melissa.walker@jll.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Test car buffer at rated speed, rated load | 8/18/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Test counterweight buffer at rated speed | 8/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Test phase 1 & 2 fire service | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 12/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 12/5/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed. | 12/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 8/18/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test elevator operation on emergency power. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work, needs repaired. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Down final limit switch roller is damaged and needs to be replaced | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Clean debris from compensation rope sheave groove in elevator pit | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Replace sheave liner on traction machine sheave due to wear. | 8/18/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery backup. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | 1 of the 2 door open buttons in the elevator cab does not work on Phase II fire service. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Right COP door close button shall function during FEO Phase II. | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Governor rope shall be replaced due to kink and breaks. | |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Full Load safety slide did not meet the minimum slide distance. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Emergency power was tested. Power did not transfer and selector did not operate and shall be repaired. (60 days reinspect) |