Inspection
Inspection Details
Equipment ID
6786
6786
Inspection Date
4/3/2025
4/3/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Jacob Schroeder
Jacob Schroeder
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
397728f4-7575-49c6-a4dd-2c02c6d25593
397728f4-7575-49c6-a4dd-2c02c6d25593
Location
Hilton Home 2 Suites
1221 Locust St, St. Louis, MO
Phone: (636) 579-3555
Email: dmgand64@gmail.com
1221 Locust St, St. Louis, MO
Phone: (636) 579-3555
Email: dmgand64@gmail.com
Owner
Attn: Brandi Jawher
Hilton Home 2 Suites
1221 Locust St, St. Louis, MO 63103
Phone: (636) 579-3555
Email: brandi.jawher@hilton.com
Hilton Home 2 Suites
1221 Locust St, St. Louis, MO 63103
Phone: (636) 579-3555
Email: brandi.jawher@hilton.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Existing cab emergency telephone does not work and shall be repaired and tested. | 6/24/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | Install counterweight guard. | 10/1/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide pit light. | 10/1/2023 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Phase 1 & Phase 2 fire service shall be tested. (Phase 1 not working, Phase 2 could not be tested). | 2/11/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 10/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | A current tested fire extinguisher is required in the machine room. | 10/1/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide annual testing of emergency power selector switch. | 2/23/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of elevators on emergency power. | 2/23/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP. | 8/14/2023 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.14.5.7 | Yes | No | Door restrictor out of adjustment, repair as needed. | 2/23/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator appears to have emergency generator power, which needs to be scheduled and tested. Re-inspection required | 2/2/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car was not answered, phone needs repaired. Re-inspection required | 2/2/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform testing of fire service to complete inspection. Re-inspection required | 2/2/2024 |
| A17.1-2016 : Elevators | 2.27 - Rope fastenings | 8.11.2.1.2(cc) | No | No | Install cable data tag on car shackles with correct size and type of rope | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator appears to have emergency generator backup power, which needs to be scheduled and tested to complete inspection. Re-inspection required | 2/20/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell is inoperable | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Yes | No | Emergency light does not work |