Inspection
Inspection Details
Equipment ID
22183
22183
Inspection Date
3/7/2025
3/7/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Tom Worsham
Tom Worsham
Relief Valve Pressure
NA
NA
Slide
Instantaneous
Instantaneous
Governor Rope Pull
60/NA - Bale
60/NA - Bale
Door Closing Force
NA
NA
External ID
f2f403da-2cd4-44e5-9a33-ae0a9d30c2aa
f2f403da-2cd4-44e5-9a33-ae0a9d30c2aa
Location
Buick Mine/ Mill
270 Forest Rd 2231, Boss, MO
Phone: (573) 626-4855
270 Forest Rd 2231, Boss, MO
Phone: (573) 626-4855
Owner
Attn: Tammy Jackson
The Doe Run Co
PO Box 500, Viburnum, MO 65566
Phone: (573) 626-2063
Email: tjackson@doerun.com
The Doe Run Co
PO Box 500, Viburnum, MO 65566
Phone: (573) 626-2063
Email: tjackson@doerun.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Pit must be enclosed with solid material. | 4/30/2020 |
| conversion | conversion | n/a | No | No | Must enclose intire hoistway. | 4/30/2020 |
| conversion | conversion | n/a | No | No | All landings must be enclosed with solid material to a height of 8'. | 4/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 12/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency light and alarm shall be operational and shall be equipped with a 4 hour battery back-up. | 7/11/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Brake coil shall not be fed off hoist motor circuit. It shall have it's own circuit with two contacts. | 1/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Rope tags and code data tag required. | 1/5/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Unit left out of service. Floor stops need to be adjusted. | 1/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No MCP provided due to no maintenance contract. | 12/4/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Unit failed 125% test. Red-tag issued. | 3/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There is no MCP due to no maintenance contract. | 12/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car alarm does not work. | 3/7/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The remainder of the annual and category 5 test shall be completed. Inspection stopped due to red tag. | 3/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car alarm does not work. Take corrective action and re-test. | 1/6/2026 |