Inspection
Inspection Details
Equipment ID
8278
8278
Inspection Date
3/4/2025
3/4/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
3799e689-b4d0-4e40-b6c2-93cc6d7127dc
3799e689-b4d0-4e40-b6c2-93cc6d7127dc
Location
St. Louis Police Department
1200 Clark Ave, St. Louis, MO
Phone: (314) 444-5521
1200 Clark Ave, St. Louis, MO
Phone: (314) 444-5521
Owner
Attn: Rick Ernst
St. Louis City of- Police Dept
1200 Market St, Room 17, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
St. Louis City of- Police Dept
1200 Market St, Room 17, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | All lighting in the machine room shall be operational. | 5/21/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current tested ABC type fire extinguisher shall be provided in the elevator machine room. Current extinguisher is expired. | 5/21/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/13/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/13/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 4/13/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The controller air conditioning shall be operational. | 4/13/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational on auxiliary power. | 5/13/2022 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | 8.11.2.1.1(y) - Seismic "earthquake direction switch" shall be operational. | 5/13/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The wiring in the pit shall be enclosed. (Note: A box cover is missing) | 4/13/2026 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | No | No | The elevator machine room shall be protected from the weather. (Note: Windows are being left open, and the equipment and machine room floor are showing signs that they have been wet, possibly from a leaky roof). | 4/13/2026 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | The car identification number shall be painted on, engraved, or securely attached to the car operating panel and shall be a minimum of 1/2" in height. (Note: The COP should be identified as car 1 as it is in the machine room). | 4/13/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/13/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 102.4 | No | No | The controller air conditioning shall be operational. | 4/13/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP Fire Service testing must be properly documented monthly on log sheet. There is no log present. | 4/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete due to elevator operational failure. Needs: all tests that include weight, buffers, pit, fire service 1 & 2, runby. | 9/1/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 3/14/2024 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency lighting shall work. | 3/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Suspension rope tail ends shall be properly seized/banded and retaining clips shall be set at proper distance. | 4/13/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/13/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work. | 9/11/2024 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. | 9/11/2024 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Cab lighting - All lamps shall work, none working. | 4/13/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have current tested and tagged fire extinguisher. No extinguisher in room or immediately adjacent to door. | 4/13/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating permit shall be obtained and displayed in the equipment room. | 4/13/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP fire service testing must be properly documented monthly on log sheet. | 4/13/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. This violation must be corrected immediately per the AHJ. | 3/4/2025 |