Inspection
Inspection Details
Equipment ID
10870
10870
Inspection Date
3/7/2025
3/7/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
NA
NA
Slide
17"
17"
Governor Rope Pull
40/500
40/500
Door Closing Force
22
22
External ID
90a72178-af18-48a3-82e8-9643d25e8c99
90a72178-af18-48a3-82e8-9643d25e8c99
Location
St. Louis City Hall
1200 Market St, St. Louis, MO
Phone: (314) 622-4635
1200 Market St, St. Louis, MO
Phone: (314) 622-4635
Owner
Attn: Rick Ernst
City of St. Louis
1200 Market St, Rm 301, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
City of St. Louis
1200 Market St, Rm 301, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace broken roller guide assembly. | 2/13/2019 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Make car door restrictor operational. | 3/29/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate in the elevator machine room. | 4/27/2020 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 1001.2(e)(2) | Yes | No | Provide code compliant minimum counterweight runby. | 5/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | The barrier in the overhead shall be restored so that no opening exists. | 4/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.20.2 | Yes | No | A suspension rope tag shall be installed. | 4/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.20.2 | Yes | No | A governor rope tag shall be installed. | 4/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | 2.27.3.2.1(c) - The smoke detector in the top of the hoistway shall only be used where sprinklers are installed. The smoke detector in the top of the hoistway shall be removed. | 4/9/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/6/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. The voice works, but video/text "yes/no" buttons are not working properly. | 5/28/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/3/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. The voice works, but video/text not working properly, answering person cannot activate camera or text/screen. | 5/21/2026 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.2 | Yes | No | Rope gripper wear swtich indicates gripper needs to be replaced. Will not reset without assistance. | 5/21/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current operating certificate shall be displayed in the equipment room in a non0-combustible frame. | 5/21/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be properly documented monthly on log sheet located in the MCP. | 5/21/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. The voice works, but video/text not working properly, answering person cannot activate camera or text/screen. | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Current operating certificate shall be displayed in the equipment room in a non0-combustible frame. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Yes | No | Fire service testing must be properly documented monthly on log sheet located in the MCP. |