Inspection
Inspection Details
Equipment ID
11252
11252
Inspection Date
4/8/2025
4/8/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Keaton Scheitlin
Keaton Scheitlin
Relief Valve Pressure
480
480
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
25
25
External ID
9cab1b2f-4b63-4b1d-9ead-0d603bbb7a17
9cab1b2f-4b63-4b1d-9ead-0d603bbb7a17
Location
Vintage Gardens
3310 N Woodbine Rd, St. Joseph, MO
Phone: (816) 279-0774
3310 N Woodbine Rd, St. Joseph, MO
Phone: (816) 279-0774
Owner
Attn: Vintage Gardens
Vintage Gardens
3310 N Woodbine Rd, St. Joseph, MO 64505
Phone: (816) 279-3330 Ext: 10
Email: atullis@sonidaliving.com
Vintage Gardens
3310 N Woodbine Rd, St. Joseph, MO 64505
Phone: (816) 279-3330 Ext: 10
Email: atullis@sonidaliving.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Fire service hat lens on car operating panel has been knocked out and is missing. | 8/19/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Need to identify unmarked floor lockout keyswitch located on car operating panel. | 8/26/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Elevator machine room door needs to be self locking. | 8/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Door unlocking rollers are missing on 1st and 2nd floor hoistway doors. | 8/19/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Need to identify floor lockout keyswitch on car operating panel to corresponding car call that it locks out. | 8/26/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door needs to be non-defeatable and self locking. | 8/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Replace missing hoistway door unlocking rollers on first and second floor. | 3/1/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No documentation of maintenance or testing in on site maintenance record log. | 7/15/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(c)(5) | No | No | Written checkout procedure for overspeed valve not on site. Needs to be kept in machine room. | 7/15/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 7/15/2022 |
| A17.1-1996 : Elevators | 3.22 - Wire rope fastening and hitch plate | 212 | No | No | INSTALL LOCK NUTS ON DEAD END OF CABLES IN HOISTWAY OVERHEAD | 7/16/2025 |