Inspection
Inspection Details
Equipment ID
1358
1358
Inspection Date
12/12/2018
12/12/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Bryan Hesskamp
Bryan Hesskamp
Relief Valve Pressure
Slide
2
2
Governor Rope Pull
25/880
25/880
Door Closing Force
NA
NA
External ID
3ce42a16-5ca4-4a86-9fe3-9e5f3d731666
3ce42a16-5ca4-4a86-9fe3-9e5f3d731666
Location
New Life Evangelistic Center
1411 LOCUST ST, SAINT LOUIS, MO
1411 LOCUST ST, SAINT LOUIS, MO
Owner
Attn: New Life Evangelistic Center
New Life Evangelistic Center
1411 LOCUST ST, SAINT LOUIS, MO 63103-2332
New Life Evangelistic Center
1411 LOCUST ST, SAINT LOUIS, MO 63103-2332
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | SAFETIES BROKEN DURING CAT 5 TEST | 12/12/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | NO VALID OPERATING CERTIFICATE POSTED | 2/7/2019 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door shall be self closing and self locking. | 2/7/2019 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | Gutter water line running over top of controller. | 2/7/2019 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room lights need to be anchored to ceiling and protective tubes over lights. | 2/7/2019 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Fire extinguisher needs to be in machine room. | 2/7/2019 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Light switch cover needs to be installed. | 2/7/2019 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Clean machine room of all dirt and debris. | 2/7/2019 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)2 | Drum machine needs to be resocketed. Reinspection required. | |||
| MO Minimum : Elevators | (I) - Pits | (I)7 | There is no stop switch in the pit. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No maintenance records on site. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency alarm does not work. | 7/6/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency light does not work. | 7/6/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Car lighting does not work. | 7/6/2022 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | There is a broken traveling cable zip tied together. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. |