Inspection
Inspection Details
Equipment ID
14288
14288
Inspection Date
3/20/2025
3/20/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
380
380
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
16
16
External ID
a015d319-5284-4cfb-8380-e33f8a725956
a015d319-5284-4cfb-8380-e33f8a725956
Location
Super 8 Motel- Union
1015 E Main St, Union, MO
Phone: (636) 583-8880
1015 E Main St, Union, MO
Phone: (636) 583-8880
Owner
Attn: Super 8 Motel-Union
Super 8 Motel-Union
1015 E Main St, Union, MO 63084
Phone: (636) 585-8880
Email: super8union@hotmail.com
Super 8 Motel-Union
1015 E Main St, Union, MO 63084
Phone: (636) 585-8880
Email: super8union@hotmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 1001.2(a)(4) | No | No | The cab flooring shall be secured to prevent potential tripping hazard. | 5/4/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/4/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 11/9/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Fire service keys shall be kept on-site. | 11/9/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Wiring diagrams shall be provided in the elevator machine room. | 11/9/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 11/9/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Water and oil appear to be in the oil leakage collection container in the pit. | 12/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Wiring diagrams shall be provided in the elevator machine room. | 4/5/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | The fire service log shall be documented monthly. | 4/5/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.5.7 Record of Oil Usage | No | No | There is no oil loss log. | 4/5/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean and free of oil and debris. Oil is collecting onto pit floor and into pit sump. | 4/5/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit and hoistway shall be kept free of dirt and rubbish. | 5/12/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | The top of car shall be kept clean and free of oil, water, dirt, and rubbish. | 5/12/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Violation: (1)MCP hasn’t been updated since 3/2022 8.6.1.2.1; ; (2)No oil loss log 8.6.1.4.1(c)(1); Cited 2024, not compliant. | 3/31/2026 |