Inspection
Inspection Details
Equipment ID
15114
15114
Inspection Date
4/8/2025
4/8/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
16"
16"
Governor Rope Pull
30/350
30/350
Door Closing Force
19
19
External ID
d65f5e88-5b03-4d83-ab81-ebcb5ddd1fc8
d65f5e88-5b03-4d83-ab81-ebcb5ddd1fc8
Location
Hilton Hotel- STL
400 Olive St, St. Louis, MO
Phone: (000) 000-0000
400 Olive St, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Ruth M. Fulton
RB STL ARCH, LLC
4124 Worth Avenue, Columbus, OH 43219
Phone: (614) 246-2577
Email: rmfulton@rockbridgecapital.com
RB STL ARCH, LLC
4124 Worth Avenue, Columbus, OH 43219
Phone: (614) 246-2577
Email: rmfulton@rockbridgecapital.com
Billing
Attn: The PENNYWELL - STL Downtown at the Arch
The PENNYWELL - STL Downtown at the Arch
400 Olive St, St. Louis, MO 63102
Phone: (314) 436-0002
Email: Zachary.Sporbert@hilton.com
The PENNYWELL - STL Downtown at the Arch
400 Olive St, St. Louis, MO 63102
Phone: (314) 436-0002
Email: Zachary.Sporbert@hilton.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Replace hoist belts--red rouge--within 30 days | 6/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform month fire service test & document on log in machine room | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean Pit | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint on seismic wires in hoistway | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 2/23/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting in machine space top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint on seismic wires in hoistway | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 1/18/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting on machine space, top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | clean car top | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Mrl Belts, clean pits all violations were written up last year with no corrections. a 30 day maximum on reinspection on all items. | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint on seismic wires in hoistway | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting in maintenance space top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Reinspection for lighting space top of hoist way failed. Management currently getting bids for electrical work to be done 30day extension has been granted from the date of this report. | 6/15/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 8/22/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 8/22/2025 |