Inspection
Inspection Details
Equipment ID
23295
23295
Inspection Date
4/10/2025
4/10/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
ee905301-265d-4ab0-a0c3-6668e0faf43e
ee905301-265d-4ab0-a0c3-6668e0faf43e
Location
Arrive Brentwood
9015 Eager Rd, St. Louis, MO
Phone: (314) 627-1070
9015 Eager Rd, St. Louis, MO
Phone: (314) 627-1070
Owner
Attn: Arrive Brentwood
Arrive Brentwood
2082 Michelson Drive, 4th Floor, Irvine, CA 92612
Phone: (314) 377-7273
Arrive Brentwood
2082 Michelson Drive, 4th Floor, Irvine, CA 92612
Phone: (314) 377-7273
Billing
Attn: Arrive Brentwood
Arrive Brentwood
9015 Eager Rd, St. Louis, MO 63144
Phone: (314) 377-7273
Email: arrivebrentwood@trinity-pm.com
Arrive Brentwood
9015 Eager Rd, St. Louis, MO 63144
Phone: (314) 377-7273
Email: arrivebrentwood@trinity-pm.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Existing battery back-up system does not work. | 2/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Provide missing lobby car number on door buck. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current elevator operating certificate. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | No | No | Provide missing bottom door fire stop. | 6/19/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 8/27/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related equipment from the machine room | 8/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | Yes | Drive machine brake is unable to hold 125% rated load. Repair or replace brake, Red-tagged, Re-inspection required | 2/24/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Existing battery backup system does not work, needs repaired. Re-inspection required | 2/24/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Existing battery backup system does not work, needs repaired. Re-inspection required | 3/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Existing battery backup system does not work, needs repaired. Re-inspection required | 4/28/2026 |