Inspection
Inspection Details
Equipment ID
19671
19671
Inspection Date
4/15/2025
4/15/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Tom Worsham
Tom Worsham
Relief Valve Pressure
350
350
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
15
15
External ID
779b2bb7-4cf9-4172-8f05-bfec93fc152e
779b2bb7-4cf9-4172-8f05-bfec93fc152e
Location
Diplomat Apartments
3530 MIAMI ST, SAINT LOUIS, MO
Phone: (573) 999-7737
3530 MIAMI ST, SAINT LOUIS, MO
Phone: (573) 999-7737
Owner
Attn: 3530 Miami Apts, LLC
3530 Miami Apts, LLC
2977 Hwy K, Ste 239, O'Fallon, MO 63368
Phone: (314) 283-4768
Alt Phone: (314) 568-6517
Email: Alan.investor@gmail.com
3530 Miami Apts, LLC
2977 Hwy K, Ste 239, O'Fallon, MO 63368
Phone: (314) 283-4768
Alt Phone: (314) 568-6517
Email: Alan.investor@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Low oil timer shall work. | 2/22/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 8/11/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.3.1.1(q) | Yes | No | Battery lowering not working needs an auxiliary contact in the disconnect | 6/22/2022 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | Yes | No | Machine room door has fire rated damper removed negating the fire rating | 6/22/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Electric base board heater has exposed wiring | 6/22/2022 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Microprocessor controller requires HVAC for temperature and humidity control | 6/22/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Label Mainline and 110 volt disconnects with feeder locations | 6/22/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Cover open knock outs in GFIC box | 6/22/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit illumination shall be 10 ft candles minimum | 6/22/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | Yes | No | Pit lighting shall be hard wired | 6/22/2022 |
| A17.1-2016 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | Yes | No | Close holes above hall stations to maintain hoistway fire rating | 6/22/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Mainline under fused controller spec's call for 100amp fusing pump and controller have peak draw of 72amps. fused at 70amps | 6/22/2022 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 3.7.1 | Yes | No | Increase Machine room Illumination to 19ft candles | 8/11/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 3.2 | Yes | No | Increase pit illumination to 10 foot candles | 8/11/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 3.2 | Yes | No | Pit light wiring required to be in conduit by NFPA 70 | 8/11/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | No | No | Label the disconnect with location of power source | 8/11/2022 |
| A17.1-2016 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 3.26.1 | No | No | Machine room heater shall be wired to meet NFPA 70 | 8/11/2022 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | No | No | No water conveying devices allowed in the machine room. This is a mod with exisiting pipes in the machine room. Must apply for a varience. Due to size of the machine room encapsulation is not an option. | 8/11/2022 |
| A17.1-2016 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | A/C unit above door has condensation running down, puddling onto machine room floor. Repair as needed. | 4/14/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work properly. | 7/11/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Phone line loss lobby unit not working, repair as needed. | 7/11/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be clean and kept clean of all debris and water | 4/14/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A written maintenance control program shall be kept on site and kept up to date | 4/14/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operational. Re-inspection required | 4/14/2026 |
| A17.1-2016 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | A/C unit above door has condensation running down, puddling onto machine room floor. Repair as needed. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be clean and kept clean of all debris and water | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Packing on the hydraulic cylinder is currently leaking oil rapidly, and shall be repaired or replaced. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Scavenger pump inside of elevator pit shall be removed and replaced with 5 gallon bucket to collect oil. |