Inspection
Inspection Details
Equipment ID
10824
10824
Inspection Date
4/16/2025
4/16/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
David Schumer
David Schumer
Relief Valve Pressure
430
430
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
17
17
External ID
ab72a2f8-62bb-4fc2-8675-94c96979583f
ab72a2f8-62bb-4fc2-8675-94c96979583f
Location
US Bank
110 W LOCKWOOD AVE, WEBSTER GROVES, MO
Phone: (314) 961-0479
110 W LOCKWOOD AVE, WEBSTER GROVES, MO
Phone: (314) 961-0479
Owner
Attn: Agnes Law
US Bank
15839 Manchester Rd, Ellisville, MO 63011
Phone: (618) 394-4521
Alt Phone: (314) 961-0479
Email: agnes.law@usbank.com
US Bank
15839 Manchester Rd, Ellisville, MO 63011
Phone: (618) 394-4521
Alt Phone: (314) 961-0479
Email: agnes.law@usbank.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency alarm bell shall work. | 5/2/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Basement and main floor doors are missing pick up rollers. | 12/3/2020 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed and needs full load test and tripping speed checked. Re-inspection required | 4/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Clean excessive oil from pump unit drip pan | 1/5/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of current state operating certificate needs to be properly displayed in machine room | 1/5/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Overspeed valve is not sealed and needs full load test and tripping speed checked. Second notice | 4/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The muffler on the pumping unit is leaking and shall be replaced or repaired | 1/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Need to clean excessive oil from pump unit drip pan | 1/5/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/5/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is not sealed and needs a full load test and tripping speed checked. Re-inspection required | 2/10/2026 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | Power Unit catch can is full. Remove oil and repair leak(s) from the muffler. | 6/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from pit and check sump pump operation. | 6/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Any pipes conveying liquids, gas, or vapors cross the overhead of the elevator equipment shall be guarded or guttered. | 6/11/2026 |