Inspection
Inspection Details
Equipment ID
14022
14022
Inspection Date
4/14/2025
4/14/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tommy Hogge
Tommy Hogge
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
21
21
External ID
b165cf2e-a8d4-4975-903e-f10399ef7d65
b165cf2e-a8d4-4975-903e-f10399ef7d65
Location
AT & T- Data Center
801 Chestnut St, St. Louis, MO
Phone: (314) 235-9992
801 Chestnut St, St. Louis, MO
Phone: (314) 235-9992
Owner
Attn: AT&T Certificate Mgmt
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (720) 874-5398
Email: att.elevators@lerchbates.com
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (720) 874-5398
Email: att.elevators@lerchbates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Alarm bell inoperative. | 10/10/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site. | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Door close chicklets are missing on both in car operating panels, replace same. | 1/13/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Door close chicklets are missing on both in car operating panels, need to be replaced | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to perform full load full speed safeties, full load car buffer, counterweight buffer, 125% brake, emergency light/alarm, emergency phone & fire service tests. Re-inspection required | 3/28/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator shall be tested on emergency power | 4/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate needs to be properly displayed in machine room | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Door close chicklets are missing on both in car operating panels. | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested for 2024. Re-inspection required | 4/14/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/13/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested for 2024. Re-inspection required | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Door close chicklets are missing on both in car operating panels, replace same. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested for 2024. Re-inspection required | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |