Inspection
Inspection Details
Equipment ID
7931
7931
Inspection Date
12/12/2018
12/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
a1041373-fae6-49ce-ad84-edb408bd6f68
a1041373-fae6-49ce-ad84-edb408bd6f68
Location
Parkway Towers Office Bldg
225 S MERAMEC AVE, CLAYTON, MO
225 S MERAMEC AVE, CLAYTON, MO
Owner
Sangita Capital Partners
7777 BONHOMME AVE STE 2300, CLAYTON, MO 63105-1963
7777 BONHOMME AVE STE 2300, CLAYTON, MO 63105-1963
Billing
Attn: Sangita Capital Partners
7777 BONHOMME AVE STE 2300, CLAYTON, MO 63105-1963
7777 BONHOMME AVE STE 2300, CLAYTON, MO 63105-1963
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Restricted opening inoperative, repair. | 9/30/2019 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | No audible signal on Phase I return. | 1/30/2020 |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Repair car door restrictor. | 1/30/2020 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Door restrictor works intermittently. Repair or replace. | 10/1/2020 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Provide pit bucket for oil collection. | 9/17/2020 | ||
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Provide feeder location on main line disconnect (NEC620.51) | 7/31/2023 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Provide feeder location on 110v. disconnect(NEC620.51). | 7/31/2023 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | x | Provide pit GFCI outlet to work properly (NEC620). | 7/31/2023 | |
A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | x | Provide existing climate control in the elevator machine room to work properly. | 7/31/2023 | |
A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | x | Seal all machine room wall and ceiling penetrations. | 7/31/2023 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Existing pipes over the elevator equipment are leaking repair as needed. | 7/31/2023 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Existing pipes to be covered to prevent future leaks/condensation from the elevator equipment. | 7/31/2023 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Provide Phase I emergency recall operations by Fire Alarm Initiating Devices (FAID) | 7/31/2023 |