Inspection
Inspection Details
Equipment ID
11312
11312
Inspection Date
4/22/2025
4/22/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
340
340
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
6c348e37-914a-463d-b4f0-899f71ea0641
6c348e37-914a-463d-b4f0-899f71ea0641
Location
Manor Care- Florissant 448
1200 Graham Rd, Florissant, MO
Phone: (314) 838-6555
1200 Graham Rd, Florissant, MO
Phone: (314) 838-6555
Owner
Attn: Manor Care
Manor Care
1200 Graham Rd, Florissant, MO 63031
Phone: (314) 838-6555
Email: ascott@mgmhealthcare.com
Manor Care
1200 Graham Rd, Florissant, MO 63031
Phone: (314) 838-6555
Email: ascott@mgmhealthcare.com
Billing
Attn: Florissant Valley Health and Rehab
Florissant Valley Health and Rehab
1200 Graham Rd, Florissant, MO 63031
Phone: (314) 838-6555 Ext: 1002
Email: brupert@mgmhealthcare.com
Florissant Valley Health and Rehab
1200 Graham Rd, Florissant, MO 63031
Phone: (314) 838-6555 Ext: 1002
Email: brupert@mgmhealthcare.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair means of two way communication with car | 5/7/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair pit lights | 7/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove oil recovery system (scavenger Pump) from pit. | 7/8/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair pit light | 7/21/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 6/28/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | 5/21/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 5/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 5/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. | 5/27/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on emergency power, annually. | 5/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work. Dials, no answer. Attempted 3 times. Phone calls front desk, calls must be answered 24/7. Reprogram to call proper monitoring agency. | 5/27/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall work. | 7/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Car door gibs to be replaced. Gibs are cutting into car sill. | 7/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | A new button needed on the basement level. | 5/8/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm shall work. | 5/8/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. | 5/8/2026 |