Inspection
Inspection Details
Equipment ID
18020
18020
Inspection Date
4/4/2025
4/4/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
27
27
External ID
e44f5531-8bc3-4bdf-82d1-2439c488c613
e44f5531-8bc3-4bdf-82d1-2439c488c613
Location
Ninth Street Parking Garage
N 9th St at Olive St, St. Louis, MO
Phone: (314) 621-3858
N 9th St at Olive St, St. Louis, MO
Phone: (314) 621-3858
Owner
Attn: INTERAGENCY
Missouri Development Finance Board-INTERAGENCY
301 W High St, Rm 680, Jefferson City, MO 65101
Phone: (000) 000-0000
Email: ap@stlouisparking.com
Missouri Development Finance Board-INTERAGENCY
301 W High St, Rm 680, Jefferson City, MO 65101
Phone: (000) 000-0000
Email: ap@stlouisparking.com
Billing
Attn: St. Louis Parking Co
St. Louis Parking Co
1617 S 3rd St, St. Louis, MO 63104
Phone: (314) 241-7777 Ext: 103
Fax: (877) 310-9169
St. Louis Parking Co
1617 S 3rd St, St. Louis, MO 63104
Phone: (314) 241-7777 Ext: 103
Fax: (877) 310-9169
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | No | Provide and record the door closing force. | 4/9/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide testing of emergency lights and bell. | 4/9/2019 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 1001.2(b)(28) | Yes | No | Provide category 1 testing of car governor. | 4/9/2019 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Repair or re-lamp light directly above the controller. | 10/6/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Provide testing of Phase 1 & Phase 2 fire service operation. | 4/9/2019 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Make the machine room lighting above the controller operational. | 10/6/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work with 24/7 support. | 4/21/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/18/2020 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | The traveling cable is damaged under the car and shall be repaired or replaced. | 10/6/2025 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | Replace the counterweight roller guides where needed for proper operation. | 5/18/2020 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)10 | Yes | No | The car safeties shall be tested. | 5/18/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/10/2020 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | The traveling cable is damaged under the car and shall be repaired or replaced. | 10/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Replace the counterweight roller guides where needed for proper operation. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 10/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The counterweight rollers are making a lot of noise. Repair or replace the rollers as needed. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | 2.26.2.22 - Counterweight buffer gas spring-return switch is broken. | 4/4/2025 |
| A17.1-1996 : Elevators | 5.6 - Governor-rope tension devices | 206.7 | No | No | 2.18.7.2 - Governor tail sheave switch shall be repaired or replaced. (held together by electrical tape) | 10/6/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the machine room. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Repair or re-lamp light directly above the controller. (Multi year violation) | 10/6/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 10/6/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP fire service testing must be properly documented monthly on log sheet. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | All machine rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 10/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 10/6/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Tighten/repair car interior handrail. | 10/6/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/6/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need to test fire service recall monthly and record on the log in the machine room. | 10/6/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate required in the machine room | |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | No | No | Machine room light shall work |