Inspection
Inspection Details
Equipment ID
17590
17590
Inspection Date
4/24/2025
4/24/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Dennis Smith Jr.
Dennis Smith Jr.
Relief Valve Pressure
410
410
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
FREIGHT DOORS
FREIGHT DOORS
External ID
f948f72f-041c-4934-9232-6f844bf4b8d0
f948f72f-041c-4934-9232-6f844bf4b8d0
Location
Triumph Foods
5302 Stockyard Expy, St. Joseph, MO
Phone: (816) 238-3040
5302 Stockyard Expy, St. Joseph, MO
Phone: (816) 238-3040
Owner
Attn: Triumph Foods
Triumph Foods
5302 Stockyards Expy, St. Joseph, MO 64504
Phone: (816) 396-2894
Email: pgomes@triumphfoods.com
Triumph Foods
5302 Stockyards Expy, St. Joseph, MO 64504
Phone: (816) 396-2894
Email: pgomes@triumphfoods.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Gland packing on jack leaks excessively and needs replacement. | 7/23/2018 |
| conversion | conversion | n/a | No | No | Provide means to keep pit free of standing water. Repair sump pump, and insure water drains to sump hole. | 7/23/2018 |
| conversion | conversion | n/a | No | No | Door unlocking pull chain boxes need to be covered and locked. | 7/23/2018 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not operate | 7/8/2020 |
| A17.1-1996 : Elevators | 1.9 - Power closing of doors or gates | 1001.2(a)(9) | No | No | Power operation of car gate will not close gate. | 5/31/2020 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Perform overspeed valve test | 1/12/2022 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room access door needs to be self-locking and non-defeatable. | 5/24/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Oil and debris present in pit, clean. | 9/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 4/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cartop light not working. | 9/30/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | REPLACE BROKEN PIT LIGHT | 5/28/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | REMOVE STANDING WATER, REPAIR SUMP PUMP, & CLEAN TRASH FROM PIT . | 5/28/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | mach room floor covered in debris on floor | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit needs to be cleanedlot of debris on floor | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | emg phone hot working not dialing out |