Inspection
Inspection Details
Equipment ID
11164
11164
Inspection Date
3/20/2025
3/20/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
NA
NA
Slide
46"
46"
Governor Rope Pull
250/800
250/800
Door Closing Force
22
22
External ID
8fdb58ab-6210-4315-a608-c40d981751a4
8fdb58ab-6210-4315-a608-c40d981751a4
Location
Pierre Laclede Center
7733 Forsyth Blvd, Clayton, MO
Phone: (314) 862-2432
7733 Forsyth Blvd, Clayton, MO
Phone: (314) 862-2432
Owner
Attn: LCP Forsyth Blvd Prop. Owner, LLC
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, CLAYTON, MO 63105
Phone: (314) 862-2432
Email: dkasten@commonwealthcommercial.com
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, CLAYTON, MO 63105
Phone: (314) 862-2432
Email: dkasten@commonwealthcommercial.com
Billing
Attn: LCP Forsyth Blvd Prop. Owner, LLC
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: owahl@commonwealthcommercial.com
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: owahl@commonwealthcommercial.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | The emergency power shall be tested with 125% capacity. | 7/28/2019 | |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Replace Ropes | 10/1/2020 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Emergency/standby power operation of the elevators shall be operational. | 10/5/2021 | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/26/2022 | ||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 4/26/2022 | ||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 4/26/2022 | ||
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Car door restrictor shall work at all floors. | 6/26/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Phase 2 switch halo to be replaced. It is currently unreadable. | 3/21/2024 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete: Began annual & Cat 5 testing, remaining testing to be finished by another inspector. Items tested - Hoistway, door, gate, restrictor, cartop, pits, light, bell, phone, comp-sheave, ring & string, terminal limits. | 3/20/2025 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Two-way communication device shall work. It dials, but no answer. | 3/20/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Repair/replace hoistway door unlocking arm at 14th floor. Unable to unlock door with key, arm/flag missing. | 3/24/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Repair/replace hoistway door unlocking arm at 14th floor. Unable to unlock door with key, arm/flag missing. (2nd notice) | |||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Expired State operating certificate in the machine room. |