MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
No
|
No
|
1) Control and operating circuits and devices shall be maintained in compliance with applicable Code requirements. 8.6.1.6.3(e) The car top operating station quit working during inspection, up & down. It shall be corrected. Ref: (G)1
|
6/3/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
No
|
No
|
2) Control and operating circuits and devices shall be maintained in compliance with applicable Code requirements. 8.6.1.6.3(e) The top directional limit seemed to not function correctly. It shall be corrected. Ref: (G)1
|
6/3/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
Yes
|
No
|
3) Inspection could not be performed because of cartop inspection station not functioning properly. Re-inspection shall be required. Ref: 5.090(1)
|
10/8/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
No
|
No
|
1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1)
|
6/3/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.2 Callbacks (Trouble Calls) Documentation
|
No
|
No
|
2) A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. Ref: 8.6.1.4.2
|
6/3/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Perform Cat 5 inspection.
|
3/4/2024
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
No
|
No
|
Provide safe and convenient access to the elevator machine room,without using the hoistway.
|
6/3/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
Provide current year tested fire extinguisher in the elevator machine room.
|
6/3/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current State Elevator Certificate.
|
6/3/2026
|