Inspection
Inspection Details
Equipment ID
1915
1915
Inspection Date
4/23/2025
4/23/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
33c9f48a-0612-49e8-bb4e-4fe1b7536c46
33c9f48a-0612-49e8-bb4e-4fe1b7536c46
Location
Hilton at the Ballpark
1 S Broadway, St. Louis, MO
Phone: (314) 421-1776
1 S Broadway, St. Louis, MO
Phone: (314) 421-1776
Owner
Attn: Lodging Hospitality Management
Lodging Hospitality Management
111 W Port Plz, Ste 500, St. Louis, MO 63146
Phone: (000) 000-0000
Lodging Hospitality Management
111 W Port Plz, Ste 500, St. Louis, MO 63146
Phone: (000) 000-0000
Billing
Attn: Hilton at the Ballpark
Hilton at the Ballpark
1 S Broadway, St. Louis, MO 63102
Phone: (314) 421-1776 Ext: 2746
Email: rguillen@hiltonstlouis.com
Hilton at the Ballpark
1 S Broadway, St. Louis, MO 63102
Phone: (314) 421-1776 Ext: 2746
Email: rguillen@hiltonstlouis.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - n/a | n/a | No | No | Pit needs to be cleaned. | 8/12/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | Cables need to be shortened. | 4/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 2/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 8.6.4.2 | No | No | Governor cables were found to be undersized. They may need to be replaced in the future. Recommendation only. | 11/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperative. | 12/3/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 3/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | 2.7.1 The elevator machine room has been damaged by the malfunctioning HVAC system resulting in drywall damage and the presence of mold. The machine room shall be repaired to meet the integrity of the room. | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | No | No | The car top escape hatch switch has been disabled. Re-enable the escape hatch switch to operate. | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | 2.27.3.1.1 The fireman’s service phase I key switch is deteriorating and shall be replaced. Reinspection required. | 4/23/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | No | No | The elevator machine room has been damaged by the malfunctioning HVAC system, resulting in drywall damage and the presence of mold. The machine room shall be repaired to meet the integrity of the room. HVAC unit in machine room still leaks at condensate pump, needing repair. | 1/13/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are at a minimum diameter, need to replace within 90 days. Re-inspection required | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to the machine room shall be clear and unobstructed. Remove all items from the stairway leading to the machine room |