Inspection
Inspection Details
Equipment ID
6085
6085
Inspection Date
4/9/2025
4/9/2025
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Ryan Teal
Ryan Teal
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
1ebf42b7-129a-4c09-8bb2-0064d293de29
1ebf42b7-129a-4c09-8bb2-0064d293de29
Location
Arch Hotel Project Owner LLC
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
Owner
Attn: Don Macbush
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 342-4637
Email: accountingstlrs@hyatt.com
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 342-4637
Email: accountingstlrs@hyatt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Bottom demarcation lights don't work | 5/1/2019 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(D) | No | No | Replace broken step tread. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Written maintenance control program shall be provided on-site for each elevator. | 12/19/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | No | Yes | Lower escalator brake torque is only 64 ft lbs. Minimum is 125 ft lbs. Replace escalator brake. Escalator removed from service & red tagged. Re-inspection required before use | 2/22/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.4 Escalator Combplates | No | No | Broken comb plate at the bottom shall be replaced | 3/29/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace broken step tread. Re-inspection required | 3/29/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Unit needs complete cleandown | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | Yes | Most, if not all, step treads have damaged fins on treads, causing sharp edges and excessive gaps between fins. Red-tagged, Re-inspection required | 10/2/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | Yes | Yes | Bottom brake torque is below minimum. Red-tagged, Re-inspection required | 10/2/2024 |
| A17.1-2016 : Elevators | 9.16 - Ceiling intersection guards | 8.6.8.9 | No | No | Replace anti climbing barricade on outer decking between units at lower end | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.14 Escalator Entrance and Egress Ends | No | No | Walkoff plate at egress end had missing/broken support braces underneath, need to be replaced | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 3/29/2024 |