Inspection
Inspection Details
Equipment ID
26897
26897
Inspection Date
4/16/2025
4/16/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
f91d8090-0e00-4f81-b7b3-1d0defd7cbc8
f91d8090-0e00-4f81-b7b3-1d0defd7cbc8
Location
Best Box
1440 Prospect Rd, Lake St. Louis, MO
Phone: (314) 302-5431
Email: nscheer@dss-bcm.com
1440 Prospect Rd, Lake St. Louis, MO
Phone: (314) 302-5431
Email: nscheer@dss-bcm.com
Owner
Attn: Nate Scheer
DSS Building Group
3167 Fee Fee Rd, Bridgeton, MO 63044
Phone: (314) 302-5431
Email: nscheer@dss-bcm.com
DSS Building Group
3167 Fee Fee Rd, Bridgeton, MO 63044
Phone: (314) 302-5431
Email: nscheer@dss-bcm.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | The overhead fasteners protruding through the ceiling of the overhead shall be cut flush to prevent a hazardous situation. | 3/18/2025 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | In electrical equipment rooms, the illumination shall not be controlled by automatic means only. Note: The machine room light shall remain on anytime the switch is in the on position. | 3/18/2025 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | x | x | Spot-type smoke detectors shall be located on the ceiling or, if on a sidewall, between the ceiling and 12 inches down from the ceiling to the top of the detector. Note: The smoke detector in the overhead does not meet these requirements. | 3/18/2025 |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | All electrical boxes in the machine room shall have covers installed and any knockout holes shall be plugged. | 3/18/2025 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Separate branch circuits shall supply the hoistway pit lighting and receptacles. Required lighting shall not be connected to the load side of a ground fault circuit interrupter. | 3/18/2025 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | x | A clear distance of not less than 4.5 inches from the centerline of the rungs, cleats, or steps to the nearest permanent object in back of the pit ladder shall be provided. | 3/18/2025 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.2 | x | The pit floor shall be flush. Note: The sump pump grate is protruding from the surface floor creating a potential tripping hazard. This shall be corrected. | 3/18/2025 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | The pit lighting shall provided an illumination of not less than 10 foot-candles at the pit floor. | 3/18/2025 | |
A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Mineral wool shall be installed in the overhead where the ceiling meets the wall per Fire Marshall. | 3/18/2025 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | x | On elevators provided with firefighters' emergency operation, a drain or sump pump shall be provided. the sump pump/drain shall have the capacity to remove a minimum of 3,000 gal/h per elevator. Note: The sump pump provided doesn't appear to meet this requirement after calculating for dynamic head. A higher capacity pump shall be provided. | 3/18/2025 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Separate branch circuits shall supply the hoistway pit lighting and receptacles. Required lighting shall not be connected to the load side of a ground fault circuit interrupter. | 4/16/2025 |