Inspection
Inspection Details
Equipment ID
11768
11768
Inspection Date
4/18/2025
4/18/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Tom Worsham
Tom Worsham
Relief Valve Pressure
370
370
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
daa2ab3b-c227-4c1d-845c-ea6f9cefca52
daa2ab3b-c227-4c1d-845c-ea6f9cefca52
Location
Beauvai's Manor on the Park
3625 Magnolia Ave, St. Louis, MO
Phone: (314) 771-2990
Email: mkleissler@beauvaismanor.com
3625 Magnolia Ave, St. Louis, MO
Phone: (314) 771-2990
Email: mkleissler@beauvaismanor.com
Owner
Attn: Jennifer Kanyuck
Beauvais Manor on the Park
3625 Magnolia Ave, St. Louis, MO 63110
Phone: (314) 771-2990 Ext: 248
Email: mkleissler@beauvaismanor.com
Beauvais Manor on the Park
3625 Magnolia Ave, St. Louis, MO 63110
Phone: (314) 771-2990 Ext: 248
Email: mkleissler@beauvaismanor.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/27/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Holes in front hoistway wall shall be sealed with approved solid material. | 10/27/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Remove the unsupported wiring in the hoistway which is not necessary for the operation of the elevator. | 10/27/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Remove oil and debris from the elevator pit. | 10/27/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Find and correct source of oil leak in the pit. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be cleaned. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The hoistway shall be cleaned. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The stop switch bezel shall be legible. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The Phase 1 and Phase 2 firefighters key switch bezels shall be legible. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/14/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 6/14/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | 6/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | No evacuation procedure in MCP. | 12/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/11/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and free of dirt and rubbish. | 12/11/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | In electrical equipment rooms, the illumination shall not be controlled by automatic means. This switch is currently a motion sensor which could turn off unexpectedly with the technician in the room. | 12/11/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water in pit. Take corrective action as needed. | 5/29/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power must be tested annually. | 5/22/2026 |