Inspection
Inspection Details
Equipment ID
17959
17959
Inspection Date
11/7/2017
11/7/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
Hanrahan Elementary
8430 Lucas & Hunt, Jennings, MO
Phone: (314) 653-8068
8430 Lucas & Hunt, Jennings, MO
Phone: (314) 653-8068
Owner
Jennings School District
2559 Dorwood, Jennings, MO 63136
2559 Dorwood, Jennings, MO 63136
Billing
Attn: Jennings School District Facilities Dept
2541 Dorwood Dr, , MO 63136
2541 Dorwood Dr, , MO 63136
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair or replace shutoff valve in machine room | 5/20/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 10/16/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Yes | Yes | Phase II fire service does not work. Did NOT Red tag. | 10/16/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. | 2/4/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 5/20/2026 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV installed, not sealed or tagged. Perform OSV test on or before next annual inspection date. | 5/20/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 5/20/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 5/20/2026 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV is due for a cat 5 weight test | 5/20/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide a written maintenance control program | 5/20/2026 |