Inspection
Inspection Details
Equipment ID
8829
8829
Inspection Date
5/9/2025
5/9/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Rodney Clay
Rodney Clay
Relief Valve Pressure
N/A
N/A
Slide
6''
6''
Governor Rope Pull
600 lbs
600 lbs
Door Closing Force
18
18
External ID
f8f94dd0-0f33-430e-9218-2a63be1f525b
f8f94dd0-0f33-430e-9218-2a63be1f525b
Location
Wesley Senior Towers
1002 Francis St, St. Joseph, MO
Phone: (816) 233-4255
1002 Francis St, St. Joseph, MO
Phone: (816) 233-4255
Owner
Attn: Wesley Senior Towers
Wesley Senior Towers
220 NW Executive Way, Lee's Summit, MO 64063
Phone: (816) 246-9220
Email: mallory@fulsonhousing.com
Wesley Senior Towers
220 NW Executive Way, Lee's Summit, MO 64063
Phone: (816) 246-9220
Email: mallory@fulsonhousing.com
Billing
Attn: Wesley Senior Towers
Wesley Senior Towers
220 NW Executive Way, Lee's Summit, MO 64063
Phone: (816) 246-9220
Email: wesley@fulsonhousing.com
Wesley Senior Towers
220 NW Executive Way, Lee's Summit, MO 64063
Phone: (816) 246-9220
Email: wesley@fulsonhousing.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency light and bell do not operate. | 6/4/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.16.8 | Yes | No | Driving machine does not safely lower and stop elevator with 125% of rated load on the elevator. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Fire hat inside elevator does not flash when machine room fire alarm initiating device is activated. | 9/23/2020 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.19.2 | Yes | Yes | Perform no load safety test. Elevator is past due for annual safety testing. | 9/23/2020 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.20.2 | Yes | No | Test tripping speed of governor and forces of pull thru | 7/19/2021 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Test unintended motion in down direction with 125% of rated load | 7/19/2021 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.20.10 | Yes | No | Perform 125% brake test | 7/19/2021 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | Yes | Perform full load safety test | 7/19/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Mark governor with identification number #2 | 8/10/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(d)(1) | No | No | Post emergency evacuation of passengers procedure in machine room | 8/10/2021 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | Yes | Unintend motion down test exceeded 48 inches. Elevator car sill stopped 76 inches below the landing sill. | 8/9/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Install dust covers on all 12 hoistway door hangers. Dustcovers are laying on top of the elevator. | 6/28/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | DOOR CLOSING FORCE IS >30 | 8/14/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | REPLACE BAD HOIST ROPES | 4/14/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | PROVIDE A SAFE MEANS FOR ENTERING & EXITING THE ROOF FROM THE HATCH LADDER | 4/14/2026 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | No | No | 2.7.3.2.1 A STAIRWAY WITH A SWING DOOR AND PLATFORM AT THE TOP LEVEL, CONFORMING TO 2.7.3.3 SHALL BE PROVIDED FROM THE TOP FLOOR OF THE BUILDING TO THE ROOF LEVEL. HATCH COVERS, AS A MEANS OF ACCESS TO ROOFS , SHALL NOT BE PERMITTED |