Inspection
Inspection Details
Equipment ID
12008
12008
Inspection Date
4/21/2025
4/21/2025
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Jarod Watson
Jarod Watson
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
463e5dd4-36cd-4a3a-9240-4ea586f82cce
463e5dd4-36cd-4a3a-9240-4ea586f82cce
Location
Boulders at Katy Trail
241-262 Scenic Cove Ln, St. Charles, MO
Phone: (000) 000-0000
241-262 Scenic Cove Ln, St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: Boulders at Katy Trail
Boulders at Katy Trail
262-296 Scenic Cove Ln, St. Charles, MO 63303
Phone: (000) 000-0000
Boulders at Katy Trail
262-296 Scenic Cove Ln, St. Charles, MO 63303
Phone: (000) 000-0000
Billing
Attn: Katy Trail Condo Association
Katy Trail Condo Association
2650 S Hanley Rd, Ste 200, St. Louis, MO 63144
Phone: (000) 000-0000
Email: mgordon@millsapartments.com
Katy Trail Condo Association
2650 S Hanley Rd, Ste 200, St. Louis, MO 63144
Phone: (000) 000-0000
Email: mgordon@millsapartments.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.8.4 | No | No | A drip pan shall be provided under the A/C unit. Water shall not accumulate on the machine room floor. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | MCP Fire service testing must be properly documented monthly on log sheet. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Wiring diagrams not present in the machine room. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking. All three machine room locks are broken. Repair or replace. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service phase 1 shall work properly. | 4/15/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve in 2024 | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 4/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | Phase 2 fire service shall work | 4/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | A/C unit over tank needs drip pan to allow ?uids to ?ow away from pump unit and not on ?oor. | 4/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. |