Inspection
Inspection Details
Equipment ID
16046
16046
Inspection Date
3/5/2025
3/5/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tony Lesniak
Tony Lesniak
Mechanic Name
Rodney Clay
Rodney Clay
Relief Valve Pressure
410
410
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
24
24
External ID
fe86677a-d511-4a39-951d-ceed752aa860
fe86677a-d511-4a39-951d-ceed752aa860
Location
Harrah's Casino- NKC
1 Riverboat Dr, North Kansas City, MO
Phone: (816) 889-4265
Alt Phone: (816) 365-6915
Email: rmurphy@harrahs.com
1 Riverboat Dr, North Kansas City, MO
Phone: (816) 889-4265
Alt Phone: (816) 365-6915
Email: rmurphy@harrahs.com
Owner
Attn: Harrah's Casino- NKC
Harrah's Casino- NKC
1 Riverboat Dr, N Kansas City, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Harrah's Casino- NKC
1 Riverboat Dr, N Kansas City, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and post a log in the machine room | 7/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | replace the emergency light battery, it is dead. | 8/17/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room needs to be updated every year | 5/17/2022 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 3.1 | No | No | Smoke damper at the top of the hoistway should be closed, and only open when the hoistway smoke detectors are activated (2.1.4) | 10/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor has been disabled, repair and adjust the door restrictor | 11/4/2024 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Adjust smoke damper in hoistway overhead to function properly | 5/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Clean the unexposed hoistway sills and door equipment | 7/18/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil absorbent pads from the pit floor | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove oil from the catch pan beneath the power unit | 7/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide updated permit in the cab or other specified location | 7/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | the painters had this elevator out of service for paint the interior, could not test, schedule reinspection |