Inspection
Inspection Details
Equipment ID
977
977
Inspection Date
4/23/2025
4/23/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Andrew Schmitz
Andrew Schmitz
Relief Valve Pressure
450
450
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21F/20R
21F/20R
External ID
73d9f31e-9df6-44de-a84d-9c9569a6e9de
73d9f31e-9df6-44de-a84d-9c9569a6e9de
Location
5353 S Lindbergh LLC
5353 S Lindbergh Blvd, St. Louis, MO
Phone: (000) 000-0000
5353 S Lindbergh Blvd, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: LCG CAPITAL MANAGEMENT
LCG CAPITAL MANAGEMENT
231 S BEMISTON STE 300, Clayton, MO 63105
Phone: (314) 408-7400 Ext: 151
Email: lcgcapitalmgmt@invoices.appfolio.com
LCG CAPITAL MANAGEMENT
231 S BEMISTON STE 300, Clayton, MO 63105
Phone: (314) 408-7400 Ext: 151
Email: lcgcapitalmgmt@invoices.appfolio.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current State certificate in machine room | 4/18/2019 |
| conversion | conversion | n/a | No | No | Repair electric eye on front car door | 4/18/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 4/18/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | No | No | Photo eye on the car door is functional during fire service recall. Photo eye must be overridden during fire service Phase 1 and 2. | 3/19/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/7/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. The pit needs to be cleaned. | 7/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cylinder packing is worn and leaking, repair/ replace as needed. | 4/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Observed standing water in the pit, confirm sump pump is working, if not-replace. | 4/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water shall not be allowed to accumulate in the pit. This is a multi-year violation. If not corrected by next annual inspection a re-inspection will be required. | 4/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump pump and cover has been removed and shall be replaced. | 4/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No MO State operating certificate in the machine room. |