Inspection
Inspection Details
Equipment ID
19
19
Inspection Date
5/13/2025
5/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Zachary Thieme
Zachary Thieme
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
30a53f40-ff4c-4a6d-a694-c311d23e845b
30a53f40-ff4c-4a6d-a694-c311d23e845b
Location
Current Resident
7232 Sarah St, Apt 301, St. Louis, MO
Phone: (000) 000-0000
7232 Sarah St, Apt 301, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Current Resident
Current Resident
7232 Sarah St, Apt 301, St. Louis, MO 63143
Phone: (000) 000-0000
Current Resident
7232 Sarah St, Apt 301, St. Louis, MO 63143
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | A current fire extinguisher shall be provided in the elevator machine room. | 10/3/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be cleaned. | 10/28/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The hoistway shall be cleaned. | 10/28/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 10/28/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/13/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 12/13/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 7/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/13/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Flexible hoses and fittings assemblies installed between the check valve or control valve and the cylinder, and that are not equipped with an overspeed valve conforming to 3.19.4.7, shall be replaced not more than 6 years beyond the installation date. A full load test will be required after the replacement. | 5/13/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 7/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room light shall be on an on/off toggle switch. Remove timed light switch. | 7/16/2025 |