Inspection
Inspection Details
Equipment ID
6524
6524
Inspection Date
12/4/2018
12/4/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Douglas Gildehaus
Douglas Gildehaus
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
79bc61f2-bb42-44fc-bb2f-f401892c5415
79bc61f2-bb42-44fc-bb2f-f401892c5415
Location
Sisters of Mercy Health Systems Building
2039 N GEYER RD, FRONTENAC, MO
2039 N GEYER RD, FRONTENAC, MO
Owner
Sisters of Mercy Health System Building
2039 N GEYER RD, FRONTENAC, MO 63131-3332
2039 N GEYER RD, FRONTENAC, MO 63131-3332
Billing
Attn: Sisters of Mercy Health System Building
2039 N GEYER RD, FRONTENAC, MO 63131-3332
2039 N GEYER RD, FRONTENAC, MO 63131-3332
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency battery back up lowering unit is inoperable. Repair or replace. Reinspection required | 12/19/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.10.2.2.1(e) | Yes | No | Cab Lighting shall work. (previous lighting shorted and to be replaced) | 1/5/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 1.6 Test Em Light/Alarm/phone. Unable to test due to lighting issue. | 1/5/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | Test Communication Loss System | 1/5/2026 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.10.2.2.1(h) | Yes | No | Test Door Closing Force | 1/5/2026 |
| A17.1-2016 : Elevators | 1.14 - Ventilation | 8.10.2.2.1(n) | Yes | No | Test Cab fan operation. | 1/5/2026 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Car door shall be restricted to not more than 4" open. Adjust bracket @ 1. | 1/5/2026 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.10.2.2.2(m) | Yes | No | Controller needs knockout hole cover. | 1/5/2026 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.10.2.2.2(ll) | Yes | No | Controller needs Alteration Code Data Plate. | 1/5/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.3 | Yes | No | Pit Sprinkler shall not be more than 24" from Heat Detector and not more than 24" from pit floor. Relocated Sprinkler head to approved location. | 1/5/2026 |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 Firefighters’ Emergency Operation | Yes | No | Test Phase 1 & 2 along with Car Stop switch bypass. | 1/5/2026 |
| ICC A117.1-2009 | 407.2 - Elevator Landing Requirements | 407.2.1.3 | Yes | No | Security Card access sensors obstruct clear access to both hall stations. Relocate. | 6/19/2025 |
| ICC A117.1-2009 | 407.2 - Elevator Landing Requirements | 407.2.1.3 | Yes | No | Security Card access sensors obstruct clear access to both hall stations. Relocate. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that operate on emergency power shall be tested. Hall station EP jewel shall be added. |