Inspection
Inspection Details
Equipment ID
8454
8454
Inspection Date
4/23/2025
4/23/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Donald Miles
Donald Miles
Relief Valve Pressure
360
360
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25F/26R
25F/26R
External ID
7f635b7a-a4f8-4b8e-8590-8e26a0574040
7f635b7a-a4f8-4b8e-8590-8e26a0574040
Location
SM Wilson
2185 HAMPTON AVE, SAINT LOUIS, MO
Phone: (314) 645-9595
2185 HAMPTON AVE, SAINT LOUIS, MO
Phone: (314) 645-9595
Owner
Attn: SW Wilson
S.M. Wilson
2185 Hampton, St. Louis, MO 63139
Phone: (314) 633-9626
Email: tracey.lewis@smwilson.com
S.M. Wilson
2185 Hampton, St. Louis, MO 63139
Phone: (314) 633-9626
Email: tracey.lewis@smwilson.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 2/20/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 10/17/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. | 2/21/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 2/21/2024 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | The overspeed valve is not sealed. It shall be tested with the rated load. | 9/27/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light shall be operational. | 2/21/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. The certificate is expired. | 2/20/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is not sealed. It shall be tested with the rated load. (2nd Notice) This violation was reported last year as well. This condition shall be corrected and re-inspected within 90 days. Failure to do so may result in revocation of your MO state operating certificate. | 10/17/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP Fire service testing must be properly documented monthly on log sheet. | 4/1/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP Fire service testing must be properly documented monthly on log sheet. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State operating certificate shall be dispayed in machine room in a non-combustible frame. |