Inspection
Inspection Details
Equipment ID
5661
5661
Inspection Date
5/14/2025
5/14/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
10
10
Governor Rope Pull
400/1200
400/1200
Door Closing Force
22
22
External ID
4b4a6ddd-443a-4aa7-9cb4-2264a2baea95
4b4a6ddd-443a-4aa7-9cb4-2264a2baea95
Location
OLTUC Bldg
1139 Olive St, St. Louis, MO
Phone: (314) 486-5623
1139 Olive St, St. Louis, MO
Phone: (314) 486-5623
Owner
Attn: Front Page Lofts, LLC
Front Page Lofts, LLC
300 N Tucker Blvd, St. Louis, MO 63101
Phone: (314) 726-0000
Email: mpmasiel@screamingeagledevelopment.com
Front Page Lofts, LLC
300 N Tucker Blvd, St. Louis, MO 63101
Phone: (314) 726-0000
Email: mpmasiel@screamingeagledevelopment.com
Billing
Attn: Front Page Lofts, LLC
Front Page Lofts, LLC
7777 Bonhomme Ave, Ste 210, St. Louis, MO 63105
Phone: (314) 920-9051
Email: mpmasiel@screamingeagledevelopment.com
Front Page Lofts, LLC
7777 Bonhomme Ave, Ste 210, St. Louis, MO 63105
Phone: (314) 920-9051
Email: mpmasiel@screamingeagledevelopment.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The elevator machine room cannot be used for storage. Remove the items (old AC units) being stored in the machine room to provide proper room for maintenance to be performed. | 7/10/2018 |
| conversion | conversion | n/a | No | No | The fire extinguisher in the machine room needs to be serviced, the last annual service tag indicates it was serviced in 2016. | 7/10/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line does not work | 3/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | Yes | Yes | Suspension ropes are showing rouge and the diameter has reduced beyond the maximum allowable amount. Replace suspension ropes. | 5/14/2025 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.20.2 | Yes | Yes | The pullout is higher than the pull through of the governor. The safetiies releasing carrier does not pull out when the jaw is fully set. | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Replace the broken springs located on the suspension rope shackles and tension the ropes | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The anti-rotation cable on the car side suspension shackles is frayed and coming apart. Replace the anti-rotation cable. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide a governor rope data tag | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete. Need to test pullout/pull through, set the safeties with a full load, fire service, 110 back up power, counter weight buffer, and emergency phone | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. | |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 8.7.3.16 | Yes | No | 8.7.2.19 - Provide a Governor rope data tag (2.18.5.3) |