Inspection
Inspection Details
Equipment ID
12988
12988
Inspection Date
5/20/2025
5/20/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
76b3a3cb-8909-4e1d-aa22-508c7dc3aa40
76b3a3cb-8909-4e1d-aa22-508c7dc3aa40
Location
Chase Park Plaza Hotel
232 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 633-1000
Email: psmith@sonesta.com
232 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 633-1000
Email: psmith@sonesta.com
Owner
Attn: Paul Smith
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1009
Alt Phone: (314) 363-4990
Email: psmith@sonesta.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1009
Alt Phone: (314) 363-4990
Email: psmith@sonesta.com
Billing
Attn: Accounts Payable
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: Psmith@Sonesta.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: Psmith@Sonesta.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Install tack wiring in conduit or duct in machine room | 3/31/2026 |
| conversion | conversion | n/a | No | No | Pit should be clean and drive remove water and debris | 3/31/2026 |
| conversion | conversion | conversion - reinspect | Yes | No | 18 repair door restrictor | 4/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency lights do not work. | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone does not work on battery back-up power. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.6.2.5 | No | No | Suspension ropes are rouged and undersized and need to be replaced. REINSPECT WITHIN 30 DAYS | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 8.6.4.11 | Yes | No | Clean elevator car top. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone - does not work with power off. | 4/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Need to shorten ropes. Re-inspection required | 4/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Elevator machine room air conditioner is not working. 90 degrees F at time of inspection. Repair | 3/31/2026 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.19.16 | Yes | No | Door restrictor inoperable (damaged), repair car door restrictor | 4/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Full load test incomplete. Test car buffer with rated load at rated speed. Test car safeties with rated load at rated speed. Test driving machine brake with 125% of rated load. | 4/3/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 5/20/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. |