Inspection
Inspection Details
Equipment ID
25712
25712
Inspection Date
4/30/2025
4/30/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17
17
External ID
b3db7620-0624-4c93-b06c-449b8b45b33b
b3db7620-0624-4c93-b06c-449b8b45b33b
Location
Avenue 64
3000 Billiken Way, O'Fallon, MO
Phone: (636) 284-7169
Email: Jpeer@thompsonthrift.com
3000 Billiken Way, O'Fallon, MO
Phone: (636) 284-7169
Email: Jpeer@thompsonthrift.com
Owner
Attn: Bonaventure
Bonaventure
Avenue 64 Leasehold LLC, 1000 Watermark drive ,O'Fallon, MO 63368
Phone: (314) 454-8029
Bonaventure
Avenue 64 Leasehold LLC, 1000 Watermark drive ,O'Fallon, MO 63368
Phone: (314) 454-8029
Billing
Attn: Jamie Bryan
Accounts Payable
1000 Watermark drive, O'Fallon, MO 63368
Phone: (317) 666-0674
Email: jamie.bryan@avenue5.com
Accounts Payable
1000 Watermark drive, O'Fallon, MO 63368
Phone: (317) 666-0674
Email: jamie.bryan@avenue5.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | Yes | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 4/20/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | Yes | No | Instructions for locating maintenance records for viewing on-site shall be posted at the means necessary for test and shall be permanently legible with characters a minimum of 3mm in height. | 4/20/2022 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.10.2.2.2(l) | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the means necessary for test at the top landing. | 4/20/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | Yes | No | A pit ladder shall be provided meeting the requirements of A17.1 2016 - 2.2.4. | 4/20/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 2.27.3.2.1( c) of A17.1 2016, A17.2 item 6, CSR 40-5.065(S)1 , NFPA 72 2013 21 .3.3, 21 .3.7, 21 .3.8, 21 .4, 21 .5 Note: A water-flow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed at the bottom of the elevator hoist-way (the elevator pit), provided the waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the water-flow switch is provided without time-delay capability. | 4/20/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Feeder locations for the lighting branch circuit shall be marked near the disconnect in the means necessary for tests. | 4/20/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Currently schematics, layout drawings, unique procedures booklet, and door operator guide are present. Provide the complete MCP approved by MO AHJ. | 7/17/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Instructions for locating maintenance records for viewing on-site shall be posted at the means necessary for test and shall be permanently legible with characters a minimum of 3mm in height. | 7/17/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | Instructions for locating maintenance records for viewing on-site shall be posted at the means necessary for test and shall be permanently legible with characters a minimum of 3mm in height. | 2/16/2024 |
| A17.1-2016 : Elevators | 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.6.4.19.17 Earthquake Operation | Yes | No | Counterweight "ring and string" earthquake detection shall work. | 2/16/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message. | 2/16/2024 |