Inspection
Inspection Details
Equipment ID
1336
1336
Inspection Date
5/20/2025
5/20/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Michael Loftin
Michael Loftin
Relief Valve Pressure
560
560
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
26
26
External ID
04c68089-2c6a-4b8f-b6af-c882ce172598
04c68089-2c6a-4b8f-b6af-c882ce172598
Location
Penleigh Branson Row
3029A W 76 Country Blvd, Branson, MO
Phone: (417) 559-2348
Email: shannon@atlasmanagementcorp.com
3029A W 76 Country Blvd, Branson, MO
Phone: (417) 559-2348
Email: shannon@atlasmanagementcorp.com
Owner
Attn: Galen Drever
Drever Atelier Angel LLC
3029 W Hwy 76, Branson, MO 65616
Phone: (646) 717-4245
Email: galen@dreverpartners.com
Drever Atelier Angel LLC
3029 W Hwy 76, Branson, MO 65616
Phone: (646) 717-4245
Email: galen@dreverpartners.com
Billing
Attn: Manuel Rivers and Jessica Koonz
Property Managers: Atlas Asset Management S Corp
641 Lexington Ave, Fl 20, New York, NY 10022
Phone: (845) 532-6934
Email: payables@atlasmanagementcorp.com
Property Managers: Atlas Asset Management S Corp
641 Lexington Ave, Fl 20, New York, NY 10022
Phone: (845) 532-6934
Email: payables@atlasmanagementcorp.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace the burnt out light tubes in the car ceiling. | 9/25/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operatoring certificate in the machine room | 10/27/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replace the emergency phone as there is no dial tone | 10/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top , inside the car, | 10/27/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the dirty pit. | 10/27/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace the burnt out light tubes in the car ceiling | 10/27/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Replace the emergency alarm bell battery | 2/7/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace the burnt out light in the car ceiling as 2 are required to be burning. | 10/27/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean up the machine room. | 10/27/2025 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | REplace the leaking packing gland. | 5/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 10/27/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace the burnt out light tubes in the machine room , 2 are required to be working. | 10/27/2025 |
| A17.1-2016 : Elevators | 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) | 8.6.4.19.6 | Yes | No | Replace the bad selector boards as we could not perform the phase ll fire test. The elevator was shut down out of service until repairs are made. And a re-inspection has been performed and approved. | 10/27/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | remove dirt and rubbish from pit floor | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | clean car top | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | provide car lighting | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | provide current state certificate |