ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
8.11.2.1.5(j)
|
Yes
|
Yes
|
Elevator red tagged due to damaged jaws during load test.
|
7/9/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.6 - Governor-rope tension devices
|
8.11.2.1.5(g)
|
No
|
No
|
Governor rope tension sheave is almost out of travel. This provides adequate governor rope tension. Shorten governor rope.
|
12/19/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
8.11.2.1.2(o)
|
Yes
|
Yes
|
Emergency brake (rope gripper) is not working. Elevator removed from service.
|
3/22/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.6 - Governor-rope tension devices
|
8.11.2.1.5(g)
|
No
|
No
|
Governor rope tension sheave is almost out of travel. This provides adequate governor rope tension. Shorten governor rope.
|
12/19/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
Yes
|
No
|
Hoist ropes shall be shortened or replaced. The counterweight is compressing the buffer 3". The ropes go into the gauge halfway so they will need to be replaced soon. Re-inspection required
|
4/30/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
No
|
No
|
Car top needs to be cleaned
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Emergency generator testing needs to be performed. Re-inspection required
|
4/30/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
Yes
|
No
|
Testing is incomplete. Following violation originally cited 2/6/24 has not been checked. Hoist ropes shall be shortened or replaced. The counterweight is compressing the buffer 3". The ropes go into the gauge halfway so they will need to be replaced soon. Re-inspection required.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
Emergency power operation shall be tested.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
To finish the 5 year full load test the following items must be tested: full load slide test, gov pull-out/pull thru, electrical trip speed, mechanical trip speed, and crush car buffer with full load.
|
|