Inspection
Inspection Details
Equipment ID
12241
12241
Inspection Date
5/13/2025
5/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
370
370
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
c307a83c-8aeb-49c2-aeba-9835a37a821b
c307a83c-8aeb-49c2-aeba-9835a37a821b
Location
SSM-St. Louis University Hospital Legacy Building
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 257-1152
Email: patrick.schubert@ssmhealth.com
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 257-1152
Email: patrick.schubert@ssmhealth.com
Owner
Attn: Brandy Kary
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 257-1152
Email: brandy.kary@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 257-1152
Email: brandy.kary@ssmhealth.com
Billing
Attn: Patrick Schubert, Director, Plant Operations
SSM SLU Hospital
1201 S Grand Blvd, St. Louis, MO 63110
Phone: (314) 257-1152
Email: patrick.schubert@ssmhealth.com
SSM SLU Hospital
1201 S Grand Blvd, St. Louis, MO 63110
Phone: (314) 257-1152
Email: patrick.schubert@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Phase II Fire service key bezel needs to be replaced | 9/3/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Door restrictor is not working. | 9/3/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light needs to be repaired. | 9/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Phase I car panel light not working. | 9/3/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated Missouri Operating Certificate in machine room | 5/20/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Repair call cancel button. Cannot shut elevator off. Only elevator in building that goes to 2 and 4 floors. Reinspect 30 days | 6/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace phase II bezel so off hold on car key switch can be read | 5/20/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Call cancel button on Phase 2 fire service does not work, needs repaired. Re-inspection required | 5/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor does not work, needs repaired. Re-inspection required | 5/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit. | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Could not access electrical panel to test emergency lights. Restricted access floor, Need to test emergency lights. Re-inspection required | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace phase II key switch bezel. All wording (off, on & hold) are missing | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace worn out and damaged car top guide rollers | 5/20/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | Yes | No | Elevator car door reopening device (light ray) does not work. Repair ore replace light ray. Re-inspection required | 5/20/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Call cancel button on phase II fire service does not work, repair needed. Cannot shut elevator down. Only elevator to move patients from floors 2 and 4. Re-inspection required | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor does not work, needs repair. Re-inspection required | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Hydraulic pump in machine room is leaking fluid, needs repaired | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery backup, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace phase II bezel so off hold on car key switch can be read |