Inspection
Inspection Details
Equipment ID
19283
19283
Inspection Date
5/6/2025
5/6/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
390
390
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
d52037fd-09bc-45a0-b76d-7fb529907c14
d52037fd-09bc-45a0-b76d-7fb529907c14
Location
City Place 5
845 N New Ballas Ct, Creve Coeur, MO
Phone: (314) 993-5800
845 N New Ballas Ct, Creve Coeur, MO
Phone: (314) 993-5800
Owner
Attn: Jessica Shaw Assistant Property Manager
SNH Medical Office Properties Trust c/o RMR Real Estate Service
1660 Lincoln St, Ste 1910, Denver, CO 80264
Phone: (314) 392-0400
Email: Jessica.shaw@cushwake.com
SNH Medical Office Properties Trust c/o RMR Real Estate Service
1660 Lincoln St, Ste 1910, Denver, CO 80264
Phone: (314) 392-0400
Email: Jessica.shaw@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Provide numbering of unit inside car. | 6/25/2019 |
| A17.1-1996 : Elevators | 2.2 Headroom | 1001.2(b)(2) | No | No | Provide guard on bulbs in machine room. | 6/25/2019 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/1/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/1/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 8/15/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/26/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall work. | 5/1/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/1/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documention shall be provided in the machine room. Missing PM/repair/callback/testing logs for 2023, 2024 and 2025. | 5/1/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have proper fire extinguisher and shall have monthly/annual test tag. | 5/1/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 5/1/2026 |