Inspection
Inspection Details
Equipment ID
14618
14618
Inspection Date
5/5/2025
5/5/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
600
600
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
8875391c-2cbb-4d61-b51c-e64ca8519a5a
8875391c-2cbb-4d61-b51c-e64ca8519a5a
Location
South Hampton Place
2727 HAMPTON AVE, SAINT LOUIS, MO
Phone: (314) 324-7555
Email: accounts@acoteam.com
2727 HAMPTON AVE, SAINT LOUIS, MO
Phone: (314) 324-7555
Email: accounts@acoteam.com
Owner
Attn: Accounting
Hampton Place Apts
2727 Hampton Ave, St. Louis, MO 63139
Phone: (618) 484-9788
Email: accounts@acoteam.com
Hampton Place Apts
2727 Hampton Ave, St. Louis, MO 63139
Phone: (618) 484-9788
Email: accounts@acoteam.com
Billing
Attn: Vince Flavin
Austin Realty
2806 S Brentwood Blvd, Brentwood, MO 63144
Phone: (314) 962-1000
Email: maintenance@austinrealtystl.com
Austin Realty
2806 S Brentwood Blvd, Brentwood, MO 63144
Phone: (314) 962-1000
Email: maintenance@austinrealtystl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | In cab emergency telephone shall work. | 5/30/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The car ceiling lighting cover is missing and requires repair or replacement. | 11/19/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the water from the pit. The pit shall be kept dry. | 11/19/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A machine room fire extinguisher is expired and shall be serviced or replaced. | 11/19/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the elevator machine room is expired. A current tested ABC type fire extinguisher shall be provided in the elevator machine room. | 6/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 6/19/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 6/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | A code data tag shall be installed. | 6/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/22/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Hoistway fascia missing between floors 3 & 4 shall be replaced. | 6/14/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve that is due for category 5 testing on or before the next annual inspection. | 6/14/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. | 10/15/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/20/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/20/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Hoistway fascia missing between floors 3 & 4 shall be replaced. | 6/20/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace damaged lower guide shoe insert. | 6/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/20/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergnecy lighting shalll work with loss of meain 120v power. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. |