Inspection
Inspection Details
Equipment ID
15211
15211
Inspection Date
12/12/2018
12/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
William Maas
William Maas
Relief Valve Pressure
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
28
28
External ID
6a1fb99d-d457-4a83-a80b-c9e676a017e6
6a1fb99d-d457-4a83-a80b-c9e676a017e6
Location
Levering Regional Health Center
1734 MARKET ST, HANNIBAL, MO
1734 MARKET ST, HANNIBAL, MO
Owner
Levering Regional Health Center
1734 MARKET ST, HANNIBAL, MO 63401-4025
1734 MARKET ST, HANNIBAL, MO 63401-4025
Billing
Attn: Levering Regional Health Center
1734 MARKET ST, HANNIBAL, MO 63401-4025
1734 MARKET ST, HANNIBAL, MO 63401-4025
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Pit light not working. | 4/11/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Sump line broken in pit causing water to leak. Poor condition. | 4/11/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service buzzer not working. Fire service works. | 3/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs elevator identification on message | 4/11/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump hole needs cover | 11/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs trash cleaned | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | In car PI not working. Repair | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Basement hall door sight guard bent. Repair | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Bad counterweight guide roller. Replace | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. New phone system | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top needs cleaning. Oil film | 6/12/2026 |