Inspection
Inspection Details
Equipment ID
20151
20151
Inspection Date
12/12/2018
12/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
William Maas
William Maas
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
f7c0971b-fca3-4c8c-aa60-191a4aab94a7
f7c0971b-fca3-4c8c-aa60-191a4aab94a7
Location
Levering Regional Health Center
1734 MARKET ST, HANNIBAL, MO
1734 MARKET ST, HANNIBAL, MO
Owner
Levering Regional Health Center
1734 MARKET ST, HANNIBAL, MO 63401-4025
1734 MARKET ST, HANNIBAL, MO 63401-4025
Billing
Attn: Levering Regional Health Center
1734 MARKET ST, HANNIBAL, MO 63401-4025
1734 MARKET ST, HANNIBAL, MO 63401-4025
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 8.11.2.1.1(c) | No | No | UP/DN directional arrows in return column missing. | 4/11/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency lighting in car not working. | 4/11/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door lock broken. Needs replaced | 3/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door lock is broken | 4/20/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs trash removed | 4/20/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Missing In case of fire don't use elevator signage needs replaced | 4/20/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Ffs buzzer not working. | 4/11/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Car capacity plate missing | 4/20/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs elevator identification on message | 4/11/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door lock broken | 11/16/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Ffs in car buzzer not working. | 5/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Emergency lowering not working. Batteries | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. New phone system | 6/12/2026 |