Inspection
Inspection Details
Equipment ID
21227
21227
Inspection Date
12/12/2018
12/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
William Gorden, Jr.
William Gorden, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
27F/26R
27F/26R
External ID
30f4c861-4357-4aca-ae62-97048dd8d35e
30f4c861-4357-4aca-ae62-97048dd8d35e
Location
Ste Genevieve County Memorial Hospital
US HWYS. Y & BODERMAN RD., BLOOMSDALE, MO
US HWYS. Y & BODERMAN RD., BLOOMSDALE, MO
Owner
Ste Genevieve County Memorial Hospital
800 STE GENEVIEVE DR, STE GENEVIEVE, MO 63670-1434
800 STE GENEVIEVE DR, STE GENEVIEVE, MO 63670-1434
Billing
Attn: Ste Genevieve County Memorial Hospital
800 STE GENEVIEVE DR, STE GENEVIEVE, MO 63670-1434
800 STE GENEVIEVE DR, STE GENEVIEVE, MO 63670-1434
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light shall work. | 1/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Car emergency lighting shall work. | 1/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | No | 2.24.8.4 - The means for manual release of the brakes shall be operational. | 3/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10 Emegency Operation and Signaling Devices | Yes | No | Counterweight displacement operation shall be functional. | 3/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 | 2/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | 2.26.1.5 Inspection Operation With Open Door Circuits. | No | No | 2.7.6.5.2 - Hoistway/Car door bypass shall be operational. | 2/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire gibs are missing from the hoistway doors. | 2/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire gibs are missing from the hoistway doors. 2nd notice. | 4/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.5 Counterweight Runby Data Plate | No | No | Counterweight Runby Data Plate in pit is missing. | 4/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 2.8.1 | No | No | Front door operator is missing its cover. Reinstall. | 4/27/2026 |