Inspection
Inspection Details
Equipment ID
15437
15437
Inspection Date
12/10/2018
12/10/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Richard Dalman
Richard Dalman
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
28/20
28/20
External ID
ced65719-05de-4bf4-aa89-c65563174ecc
ced65719-05de-4bf4-aa89-c65563174ecc
Location
UMKC University Way
1011 EAST 51ST, KANSAS CITY, MO
1011 EAST 51ST, KANSAS CITY, MO
Owner
Attn: UMKC- Parking Structure
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 1001.2(d)(2) | No | No | Replace broken glass in lower landing hoistway door | 11/21/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Perform monthly fire service test and post test log in the machine room | 11/21/2025 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 1001.2(d)(2) | No | No | Replace broken glass in hoistway door at the bottom landing | 11/21/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | replace the emergency light battery, it is dead | 11/21/2025 |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 110.11a | No | No | the hoistway door sills need to be grouted at both landings, there is no grout between the sill and the landing floor | 11/21/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the copy of the state operating certificate in the machine room is to be updated annually | 11/21/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | replace broken glass in bottom landing hoistway door, this is the 3rd year that this violation has been written up. this is a broken glass door not a sight window | 10/12/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | The next 5 year test on the overspeed valve will be in 2025 | 10/12/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate on display in the machine room expired in 2014, update with current copy annually when received from the state | 11/21/2025 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | can not read the marking on the fire service phase 1 keyswitch collar, replace collar | 11/21/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate in the machine room expired in 2014, update with current state operating certificate when received | 11/21/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | The emergency battery pack is not working. | 11/21/2025 |