Inspection
Inspection Details
Equipment ID
12871
12871
Inspection Date
5/28/2025
5/28/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
15
15
External ID
c27eaf4e-bee3-4188-932b-a34b5cdbbdfc
c27eaf4e-bee3-4188-932b-a34b5cdbbdfc
Location
Merchandise Mart Apartments LLC
1000 Washington Ave, St. Louis, MO
Phone: (314) 350-6600
Alt Phone: (314) 350-6600
Email: sixcord@opstl.com
1000 Washington Ave, St. Louis, MO
Phone: (314) 350-6600
Alt Phone: (314) 350-6600
Email: sixcord@opstl.com
Owner
Attn: Mark Milford Six Cord Apartments
Merchandise Mart Apartments LLC
1000 Washington Ave, St. Louis, MO 63101
Phone: (314) 350-6600
Alt Phone: (314) 350-6600
Email: sixcord@opstl.com
Merchandise Mart Apartments LLC
1000 Washington Ave, St. Louis, MO 63101
Phone: (314) 350-6600
Alt Phone: (314) 350-6600
Email: sixcord@opstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 11/7/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The fireman service phase I key switch housing is damaged and shall be replaced. Reinspection required. | 7/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire” is missing on a number of landings. Install signage that conforms to the building code this elevator was installed to meet. | 11/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The elevator car top is covered with an extreme amount of dust and shall be cleaned. | 11/7/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 8/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Handrail on back is loose and shall be repaired | 11/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove non elevator related materials from machine room | 11/7/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 11/7/2023 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Handrail on back is loose and shall be corrected | 11/7/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide testing of the elevator on emergency power. | |
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | Yes | No | Provide testing of the elevator emergency power selector switch ( located in the Fire Command Room). |